ANALISIS PENGUJIAN PROTEKSI SALURAN TRANSMISI MENGGUNAKAN DISTANCE RELAY PADA BAY LINE SENGKOL–KUTA DI GI 150 KV SENGKOL

Authors

  • Haris Setyo Adi Jurusan Teknik Elektro Universitas Mataram
  • Agung Budi Muljono

DOI:

https://doi.org/10.23960/jitet.v13i3S1.8003

Abstract Views: 74 File Views: 59

Keywords:

Distance Relay, Proteksi Saluran Transmisi, Omicron CMC 356, IEC 60255-121:2014

Abstract

Distance relay is a crucial component in the protection system of high-voltage transmission lines. Faults on transmission lines can cause equipment damage and disrupt the continuity of power supply. This study aims to evaluate the performance and characteristics of the distance relay on the Sengkol–Kuta transmission line bay at the 150 kV Sengkol Substation. The testing method employed is shutdown testing, referring to IEC 60255-121:2014 and SPLN No.15 of 2014 standards. The test was conducted using an Omicron CMC 356 test set and Test Universe software. The protection zones examined include zone-1 and zone-2, with impedance and operating time parameters adjusted according to the line length. The results indicate that the MiCOM P543 relay operates accurately and responsively to simulated faults, as demonstrated by Mho and Quadrilateral characteristic curves that align with the protection system boundaries. These findings confirm that the implemented distance relay protection system functions optimally in fault detection and contributes to maintaining the reliability of the power system.

Downloads

Download data is not yet available.

References

S. E. M. Yusuf, “Analisis Proteksi Rele Jarak Pada Saluran Udara Tegangan Tinggi 150 kV,” Sinusoida, vol. XXII, no. 83, 2020.

Nabila Khoirunnisa, Nelli Inayah, Farid Wiherdiansyah, I Kadek Dwi Adyano, and Didik Aribowo, “Studi Literatur Tentang Jenis dan Penyebab Gangguan Pada Saluran Transmisi,” Surya Tek., vol. 11, no. Studi Literatur Tentang Jenis dan Penyebab Gangguan Pada Saluran Transmisi, pp. 569–573, 2024.

D. Romdhani, Supriyatna, and A. B. Muljono, “Proteksi Rele Jarak Pada Jaringan Sutt 150 Kv Gi Ampenan – Pltu Lombok Energy Dynamic (Led),” Dielektrika, vol. 8, no. 1, p. 36, 2021, doi: 10.29303/dielektrika.v8i1.263.

C. P. Maharani, I. M. A. Nrartha, S. I. Nugroho, and A. Hasibuan, “PENGUJIAN TEGANGAN TEMBUS MINYAK TRAFO PADA BAY TRAFO 1 DI GI 150 kV TANJUNG,” J. Inform. dan Tek. Elektro Terap., vol. 12, no. 3, 2024, doi: 10.23960/jitet.v12i3.4347.

R. A. Wahyuningsih, Supriyatna, and A. B. Muljono, “Proteksi Rele Jarak (Distance Relay) Pada Saluran Udara Tegangan Tinggi (SUTT) 150 kV Sistem Kelistrikan Lombok,” Dielektrika, vol. 7, no. 1, p. 15, 2020, doi: 10.29303/dielektrika.v7i1.230.

N. Benedicta, “Analisis Scanning Setting Proteksi Distance Relay Pada Penghantar 150 kV Gardu Induk Garuda Sakti Ke Gardu Induk Balai Pungut,” 2021, [Online]. Available: http://repository.uin-suska.ac.id/id/eprint/54191

G. Agustina, S. Anisah, and A. S. P. Tarigan, “Analisa Hasil Pemeliharaan Shutdown Testing Dengan Alat Uji Omicron CMC 356 Pada Relay Distance Bay Line 150 Kv Jantho Di Gi Sigli,” J. Electr. Syst. Control Eng., vol. 8, no. 2, pp. 271–279, 2025, doi: 10.31289/jesce.v6i2.14168.

M. F. R. Pratama, M. A. S. Yudono, and H. B. Tambunan, “Analisis Kegagalan Kerja Relay Auto Reclose Pmt 7Ab3 Di Gistet Saguling,” J. Inform. dan Tek. Elektro Terap., vol. 12, no. 3S1, 2024, doi: 10.23960/jitet.v12i3s1.5224.

A. S. Sampeallo, Nursalim, and P. J. Fischer, “Analisis Gangguan Hubung Singkat Pada Jaringan Pemakaian Sendiri Pltu Bolok PT. SMSE (IPP) Unit 3 Dan 4 Menggunakan Software Etap 12.6.0,” no. 0380, 2015.

J. L. T. J. D. Blackburn, Protective Relaying : Principles and Applications Third Edition. 2006. doi: 10.1002/9781119806721.ch12.

PLN, “Pedoman dan Petunjuk Sistem Proteksi Transmisi dan Gardu Induk Jawa Bali,” PT PLN, no. September, p. 513, 2013.

PLN, “Buku Pedoman Pemeliharaan Proteksi dan Kontrol Penghantar,” Jakarta PT. PLN, no. 0520, pp. 3–4, 2014.

I. A. Wibowo, “Optimasi Keandalan Proteksi Rele Distance Pada Penghantar 150 Kv Sunyaragi – Jatigede,” 2024.

E. Criyanto, Supriyatna, and A. B. Muljono, “Analisis Koordinasi Isolasi Di Gardu Induk Kuta Terhadap Tegangan Lebih Akibat Sambaran Petir Pada Saluran Transmisi 150 kV,” Dielektrika, vol. 7, no. 1, pp. 64–72, 2020.

International Electrotechnical Commission (IEC), “Measuring relays and protection equipment – Part 121: Functional requirements for distance protection,” Geneva, Switzerland, 2014.

L. Andreansyah, Gunawan, and B. Sukoco, “Analisis Rele Jarak Sebagai Proteksi Pada Jaringan Transmisi Saluran Udara Tegangan Tinggi 150 Kv Gardu Induk Randu Garut-Weleri,” Konf. Ilm. Mhs. Unissula 2, pp. 133–140, 2019.

Downloads

Published

2025-10-19

How to Cite

Adi, H. S., & Muljono, A. B. (2025). ANALISIS PENGUJIAN PROTEKSI SALURAN TRANSMISI MENGGUNAKAN DISTANCE RELAY PADA BAY LINE SENGKOL–KUTA DI GI 150 KV SENGKOL. Jurnal Informatika Dan Teknik Elektro Terapan, 13(3S1). https://doi.org/10.23960/jitet.v13i3S1.8003

Issue

Section

Articles